|
|
|
Categories
|
|
Information
|
|
Featured Product
|
|
|
 |
|
|
There are currently no product reviews.
 ;
Good quality. Quick service. I recommend to everyone.
 ;
Very good quality scan of the document. I am very pleased with what I got.
 ;
PDF Contains
Technical Data, Mechanical data, Detailed Circuit diagram with components value, PCB layout. Actual PCBs Print. Component List, Spare parts code list and Input output detail. It cover LBB1211, LBB1212, LBB1213, LBB1216, LBB1217.
It is the actual Service Manual for SQ10
 ;
very good manual with clear electrical schemes. Very helpful to find wat was wrong inside my microwave.
 ;
Hi, thankyou for providing the Nordmende Globetrotter original manufacturer's repair manual. Quality is very good and sharp - the PDF file was comfortably small to download. The only question is: why did it take so long to become ready for download?? Many thanks anyway, I fixed the fault in the radio thanks to the circuit.
regards: Nick
2. Flaring Work and Connection of Piping
1) Flaring work
Main cause for gas leakage is due to defect in flaring work. Carry out correct flaring work in the following procedure. 1. Cut the pipes and the cable. Use the piping kit accessory or the pipes purchased locally. Measure the distance between the indoor and the outdoor unit. Cut the pipes a little longer than measured distance. Cut the cable 1.5m longer than the pipe length.
Copper pipe 90° Slanted Uneven Rough
4. Flaring work Carry out flaring work using flaring tool as shown below. Outside diameter mm ø6.35 ø9.52 ø12.7 ø15.88 inch 1/4 3/8 1/2 5/8 A mm 0 ~ 0.5 0 ~ 0.5 0 ~ 0.5 0 ~ 1.0
Firmly hold copper pipe in a die in the dimension shown in the table above.
"A"
Handle Bar Bar Yoke Cone Copper pipe Clamp handle Red arrow mark
2. Burrs removal Completely remove all burrs from the cut cross section of pipe/tube. Put the end of the copper tube/pipe in a downward direction as you remove burrs in order to avoid dropping burrs into the tubing.
Pipe Reamer
5. Check
Point down
Compare the flared work with figure below. If flare is noted to be defective, cut off the flared section and do flaring work again.
3. Putting nut on Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal. (not possible to put them on after flaring work)
Flare nut Copper tube
Even length all round Inclined Surface Cracked Uneven damaged thickness Smooth all round Inside is shiny without scratches
= Improper flaring =
- 27 -
|
|
 |
> |
|